Language selection

Government of Canada

Search

Energy Efficiency Regulations, 2016 (SOR/2016-311)

Regulations are current to 2025-10-28 and last amended on 2025-10-09. Previous Versions

PART 2Energy-Using Products (continued)

DIVISION 2Air Conditioners, Condensing Units and Chillers (continued)

SUBDIVISION ARoom Air Conditioners (continued)

Marginal note:Cooling capacity category

 For the purposes of these Regulations, the cooling capacity category of a room air conditioner is the applicable cooling capacity range set out in

  • (a) Table 2 of CSA C368.1, if the product was manufactured before June 1, 2014;

  • (b) Table 2 to Part 2 of TSD D2SA001, if the product is manufactured on or after June 1, 2014 and before May 26, 2026; and

  • (c) Table 3 to Part 2 of TSD D2SA001, if the product is manufactured on or after May 26, 2026.

Marginal note:Energy-using product

  •  (1) A room air conditioner is prescribed as an energy-using product.

  • Marginal note:Limit

    (2) However, for the purposes of sections 4, 5, 112, 114 and 115, a room air conditioner is not considered to be an energy-using product unless it is manufactured on or after February 3, 1995.

Marginal note:Energy efficiency standards

  •  (1) The energy efficiency standards set out in column 2 of the table to this section apply to room air conditioners that are manufactured during the periods set out in column 3.

  • Marginal note:Testing standard

    (2) A room air conditioner complies with the energy efficiency standard if it meets that standard when tested in accordance with testing procedures established by the standard set out in column 1 that are applicable to a room air conditioner as defined in section 108.

    TABLE

    Column 1Column 2Column 3
    ItemTesting StandardEnergy Efficiency StandardPeriod of Manufacture
    1CSA C368.1CSA C368.1, Table 2, second columnOn or after February 3, 1995 and before June 1, 2014
    2Part 1 of TSD D2SA001Part 2 of TSD D2SA001On or after June 1, 2014

Marginal note:Information

 For the purpose of subsection 5(1) of the Act, the information set out in column 3 of the table to this section must be collected in accordance with the standard or provision set out in column 2 and provided to the Minister in respect of a room air conditioner described in column 1.

TABLE

Column 1Column 2Column 3
ItemEnergy-using ProductTesting StandardInformation
1Room air conditioners manufactured before June 1, 2014CSA C368.1, for information set out in paragraphs (b) to (d)
  • (a) type;

  • (b) power input;

  • (c) cooling capacity, in kW (Btu/h); and

  • (d) energy efficiency ratio.

2Room air conditioners manufactured on or after June 1, 2014

Part 1 of TSD D2SA001, for information set out in paragraphs (b) and (c)

  • (a) type;

  • (b) cooling capacity, in kW (Btu/h); and

  • (c) the product’s CEER.

Marginal note:Form of labelling

 A room air conditioner must be labelled

  • (a) if it was manufactured before June 1, 2014, in the form set out in Schedule 2; or

  • (b) if it is manufactured on or after June 1, 2014, in the form set out in Schedule 3.

Marginal note:Manner of labelling

 The label must be displayed on the principal display panel of the product’s package

  • (a) by printing it on that panel; or

  • (b) by affixing to the panel an adhesive tag that is printed on paper that meets the requirements of subsection 14(1) and that has an adhesion capacity that is sufficient to prevent the tag from being dislodged from the packaging under normal handling conditions.

SUBDIVISION BLarge Air Conditioners

Marginal note:Definitions

 The following definitions apply in this Subdivision.

AHRI 340/360

AHRI 340/360 means the AHRI standard ANSI/AHRI 340/360-2007 entitled Performance Rating of Commercial and Industrial Unitary Air-Conditioning and Heat Pump Equipment. (AHRI 340/360)

CSA C746-17

CSA C746-17 means the CSA standard CAN/CSA-C746-17 entitled Energy performance rating for large and single packaged vertical air conditioners and heat pumps. (CSA C746-17)

IEER

IEER means the integrated energy efficiency ratio, expressed in British thermal units per watt hour, that constitutes a single number cooling part-load efficiency metric of a large air conditioner. (IEER)

large air conditioner

large air conditioner means a commercial or industrial unitary air conditioner with a cooling capacity of at least 19 kW (65,000 Btu/h) but less than 223 kW (760,000 Btu/h). It does not include a single package vertical air conditioner. (climatiseur de grande puissance)

10 C.F.R. Appendix A

10 C.F.R. Appendix A means Appendix A to Subpart F, Part 431 of Title 10 to the United States Code of Federal Regulations, entitled Uniform Test Method for the Measurement of Energy Consumption of Air-Cooled Small (≥65,000 Btu/h), Large, and Very Large Commercial Package Air Conditioning and Heating Equipment, as amended from time to time. (appendice A 10 C.F.R.)

Marginal note:Energy-using product

  •  (1) A large air conditioner is prescribed as an energy-using product.

  • Marginal note:Limits

    (2) However, for the purposes of sections 4, 5 and 118, a large air conditioner is not considered to be an energy-using product unless

    • (a) in the case of a large air conditioner with a cooling capacity of less than 70 kW, it is manufactured on or after December 31, 1998; and

    • (b) in the case of a large air conditioner with a cooling capacity of 70 kW or more, it is manufactured on or after January 1, 2010.

Marginal note:Energy efficiency standards — cooled by air

  •  (1) The energy efficiency standards set out in column 3 of Table 1 to this section apply to large air conditioners that are cooled by air and described in column 1 and that are manufactured during the period set out in column 4.

  • Marginal note:Energy efficiency standards — cooled by water

    (2) The energy efficiency standards set out in column 3 of Table 2 to this section apply to large air conditioners that are cooled by water and described in column 1 and that are manufactured during the period set out in column 4.

  • Marginal note:Energy efficiency standards — cooled by evaporation

    (2.1) The energy efficiency standards set out in column 3 of Table 3 to this section apply to large air conditioners that are cooled by evaporation and described in column 1 and that are manufactured during the period set out in column 4.

  • Marginal note:Testing standard

    (3) A large air conditioner complies with the energy efficiency standard set out in column 3 if it meets that standard when tested in accordance with testing procedures established by the standard set out in column 2 that are applicable to a large air conditioner as defined in section 116.

    TABLE 1

    Column 1Column 2Column 3Column 4
    ItemEnergy-using ProductTesting StandardEnergy Efficiency StandardPeriod of Manufacture
    1Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and either without a heating section or with an electric heating sectionCSA C746-98Energy efficiency ratio ≥ 10.3On or after December 31, 1998 and before January 1, 2010
    2Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and either without a heating section or with an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 11.2

    IEER ≥ 11.4

    On or after January 1, 2010 and before January 1, 2018
    3Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and either without a heating section or with an electric heating sectionCSA C746-17

    Energy efficiency ratio ≥ 11.2

    IEER ≥ 12.9

    On or after January 1, 2018 and before January 1, 2026
    4Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and either without a heating section or with an electric heating sectionCSA C746-17 or 10 C.F.R. Appendix A

    Energy efficiency ratio ≥ 11.2

    IEER ≥ 14.8

    On or after January 1, 2026
    5Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and either without a heating section or with an electric heating sectionCSA C746-98Energy efficiency ratio ≥ 9.7On or after December 31, 1998 and before January 1, 2010
    6Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and either without a heating section or with an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 11.0

    IEER ≥ 11.2

    On or after January 1, 2010 and before January 1, 2018
    7Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and either without a heating section or with an electric heating sectionCSA C746-17

    Energy efficiency ratio ≥ 11.0

    IEER ≥ 12.4

    On or after January 1, 2018 and before January 1, 2026
    8Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and either without a heating section or with an electric heating sectionCSA C746-17 or 10 C.F.R. Appendix A

    Energy efficiency ratio ≥ 11.0

    IEER ≥ 14.2

    On or after January 1, 2026
    9Large air conditioners that have a cooling capacity of ≥ 70 kW and < 223 kW and either without a heating section or with an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 10.0

    IEER ≥ 10.1

    On or after January 1, 2010 and before January 1, 2018
    10Large air conditioners that have a cooling capacity of ≥ 70 kW and < 223 kW and either without a heating section or with an electric heating sectionCSA C746-17

    Energy efficiency ratio ≥ 10.0

    IEER ≥ 11.6

    On or after January 1, 2018 and before January 1, 2026
    11Large air conditioners that have a cooling capacity of ≥ 70 kW and < 223 kW and either without a heating section or with an electric heating sectionCSA C746-17 or 10 C.F.R. Appendix A

    Energy efficiency ratio ≥ 10.0

    IEER ≥ 13.2

    On or after January 1, 2026
    12Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and a heating section other than an electric heating sectionCSA C746-98Energy efficiency ratio ≥ 10.1On or after December 31, 1998 and before January 1, 2010
    13Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and a heating section other than an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 11.0

    IEER ≥ 11.2

    On or after January 1, 2010 and before January 1, 2018
    14Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and a heating section other than an electric heating sectionCSA C746-17

    Energy efficiency ratio ≥ 11.0

    IEER ≥  12.7

    On or after January 1, 2018 and before January 1, 2026
    15Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and a heating section other than an electric heating sectionCSA C746-17 or 10 C.F.R. Appendix A

    Energy efficiency ratio ≥ 11.0

    IEER ≥  14.6

    On or after January 1, 2026
    16Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and a heating section other than an electric heating sectionCSA C746-98Energy efficiency ratio ≥ 9.5On or after December 31, 1998 and before January 1, 2010
    17Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and a heating section other than an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 10.8

    IEER ≥ 11.0

    On or after January 1, 2010 and before January 1, 2018
    18Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and a heating section other than an electric heating sectionCSA C746-17

    Energy efficiency ratio ≥ 10.8

    IEER ≥ 12.2

    On or after January 1, 2018 and before January 1, 2026
    19Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and a heating section other than an electric heating sectionCSA C746-17 or 10 C.F.R. Appendix A

    Energy efficiency ratio ≥ 10.8

    IEER ≥ 14.0

    On or after January 1, 2026
    20Large air conditioners that have a cooling capacity of ≥ 70 kW and < 223 kW and a heating section other than an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 9.8

    IEER ≥ 9.9

    On or after January 1, 2010 and before January 1, 2018
    21Large air conditioners that have a cooling capacity of ≥ 70 kW and < 223 kW and a heating section other than an electric heating sectionCSA C746-17

    Energy efficiency ratio ≥ 9.8

    IEER ≥ 11.4

    On or after January 1, 2018 and before January 1, 2026
    22Large air conditioners that have a cooling capacity of ≥ 70 kW and < 223 kW and a heating section other than an electric heating sectionCSA C746-17 or 10 C.F.R. Appendix A

    Energy efficiency ratio ≥ 9.8

    IEER ≥ 13.0

    On or after January 1, 2026

    TABLE 2

    Column 1Column 2Column 3Column 4
    ItemEnergy-using ProductTesting StandardEnergy Efficiency StandardPeriod of Manufacture
    1Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and either without a heating section or with an electric heating sectionCSA C746-98Energy efficiency ratio ≥ 11.5On or after December 31, 1998 and before January 1, 2010
    2Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and either without a heating section or with an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 11.5

    IEER ≥ 11.7

    On or after January 1, 2010 and before January 1, 2018
    3Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and either without a heating section or with an electric heating sectionCSA C746-17

    Energy efficiency ratio ≥ 12.1

    IEER ≥ 11.7

    On or after January 1, 2018
    4Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and either without a heating section or with an electric heating sectionCSA C746-98Energy efficiency ratio ≥ 11.0On or after December 31, 1998 and before January 1, 2010
    5Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and either without a heating section or with an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 11.0

    IEER ≥ 11.2

    On or after January 1, 2010 and before January 1, 2018
    6Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and either without a heating section or with an electric heating sectionCSA C746-17

    Energy efficiency ratio ≥ 12.5

    IEER ≥ 11.2

    On or after January 1, 2018
    7Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and a heating section other than an electric heating sectionCSA C746-98Energy efficiency ratio ≥ 11.3On or after December 31, 1998 and before January 1, 2010
    8Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and a heating section other than an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 11.3

    IEER ≥ 11.5

    On or after January 1, 2010 and before January 1, 2018
    9Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and a heating section other than an electric heating sectionCSA C746-17

    Energy efficiency ratio ≥ 11.9

    IEER ≥ 11.5

    On or after January 1, 2018
    10Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and a heating section other than an electric heating sectionCSA C746-98Energy efficiency ratio ≥ 10.8On or after December 31, 1998 and before January 1, 2010
    11Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and a heating section other than an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 10.8

    IEER ≥ 11.0

    On or after January 1, 2010 and before January 1, 2018
    12Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and a heating section other than an electric heating sectionCSA C746-17

    Energy efficiency ratio ≥ 12.3

    IEER ≥ 11.0

    On or after January 1, 2018
    13Large air conditioners that have a cooling capacity of ≥ 70 kW and < 223 kW and either without a heating section or with an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 11.0

    IEER ≥ 11.1

    On or after January 1, 2010 and before January 1, 2018
    14Large air conditioners that have a cooling capacity of ≥ 70 kW and < 223 kW and either without a heating section or with an electric heating sectionCSA C746-17

    Energy efficiency ratio ≥ 12.4

    IEER ≥ 11.1

    On or after January 1, 2018
    15Large air conditioners that have a cooling capacity of ≥ 70 kW and < 223 kW and a heating section other than an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 10.8

    IEER ≥ 10.9

    On or after January 1, 2010 and before January 1, 2018
    16Large air conditioners that have a cooling capacity of ≥ 70 kW and < 223 kW and a heating section other than an electric heating sectionCSA C746-17

    Energy efficiency ratio ≥ 12.2

    IEER ≥ 10.9

    On or after January 1, 2018

    TABLE 3

    Column 1Column 2Column 3Column 4
    ItemEnergy-using ProductTesting StandardEnergy Efficiency StandardPeriod of Manufacture
    1Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and either without a heating section or with an electric heating sectionCSA C746-98Energy efficiency ratio ≥ 11.5On or after December 31, 1998 and before January 1, 2010
    2Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and either without a heating section or with an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 11.5

    IEER ≥ 11.7

    On or after January 1, 2010 and before January 1, 2018
    3Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and either without a heating section or with an electric heating sectionCSA C746-17

    Energy efficiency ratio ≥ 12.1

    IEER ≥ 11.7

    On or after January 1, 2018
    4Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and either without a heating section or with an electric heating sectionCSA C746-98Energy efficiency ratio ≥ 11.0On or after December 31, 1998 and before January 1, 2010
    5Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and either without a heating section or with an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 11.0

    IEER ≥ 11.2

    On or after January 1, 2010 and before January 1, 2018
    6Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and either without a heating section or with an electric heating sectionCSA C746-17

    Energy efficiency ratio ≥ 12.0

    IEER ≥ 11.2

    On or after January 1, 2018
    7Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and a heating section other than an electric heating sectionCSA C746-98Energy efficiency ratio ≥ 11.3On or after December 31, 1998 and before January 1, 2010
    8Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and a heating section other than an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 11.3

    IEER ≥ 11.5

    On or after January 1, 2010 and before January 1, 2018
    9Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and a heating section other than an electric heating sectionCSA C746-17

    Energy efficiency ratio ≥ 11.9

    IEER ≥ 11.5

    On or after January 1, 2018
    10Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and a heating section other than an electric heating sectionCSA C746-98Energy efficiency ratio ≥ 10.8On or after December 31, 1998 and before January 1, 2010
    11Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and a heating section other than an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 10.8

    IEER ≥ 11.0

    On or after January 1, 2010 and before January 1, 2018
    12Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and a heating section other than an electric heating sectionCSA C746-17

    Energy efficiency ratio ≥ 11.8

    IEER ≥ 11.0

    On or after January 1, 2018
    13Large air conditioners that have a cooling capacity of ≥ 70 kW and < 223 kW and either without a heating section or with an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 11.0

    IEER ≥ 11.1

    On or after January 1, 2010 and before January 1, 2018
    14Large air conditioners that have a cooling capacity of ≥ 70 kW and < 223 kW and either without a heating section or with an electric heating sectionCSA C746-17

    Energy efficiency ratio ≥ 11.9

    IEER ≥ 11.1

    On or after January 1, 2018
    15Large air conditioners that have a cooling capacity of ≥ 70 kW and < 223 kW and a heating section other than an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 10.8

    IEER ≥ 10.9

    On or after January 1, 2010 and before January 1, 2018
    16Large air conditioners that have a cooling capacity of ≥ 70 kW and < 223 kW and a heating section other than an electric heating sectionCSA C746-17

    Energy efficiency ratio ≥ 11.7

    IEER ≥ 10.9

    On or after January 1, 2018
 

Page Details